Glossary

COP

The COP or ‘Coefficient of performance’ is a measure if energy-efficiency, and found by dividing the useful heat output by the electrical energy input. e.g. a heat pump that produces 4 kWatts of heat for 1 kWatt of electrical input power has a COP of 4.  The COP will vary depending on the operating temperatures of the system.  Look out for optimistic figures quoted in unfairly favorable operating conditions

SPF

Seasonal Performance Factor is similar to COP, but is an average figure taken over the year. It is the total energy input (including pumps and any supplementary electric boost heaters) compared with the total useful heat output deliverd to the building.

Efficiency

The word “Efficiency” can be used rather loosely, but on this site, it is the ratio of useful output to energy input. e.g. if an open fireplace loses half its energy up the chimney it is said to be 50% efficient. A bright light bulb might be efficient at lighting a space, but we generally talk of the energy-efficiency. e.g. an old 100W lightbulb might emit only 5W of light. It is therefore only 5% efficient.

Source, or heat source

This is wherever the heat is being extracted from. e.g. the outside air, river or ground. Sometimes referred to as an ambient source.     It could also be recovered heat from extract air or effluent water etc.

Geothermal

This is defined as ‘heat from the ground’. Proper geothermal is heat from the earth’s core extracted from very deep in the ground, as in the steam that powers the whole of Iceland. The term is sometimes used (wrongly to my mind) to describe Ground Source Heat Pumps.

Horizontal collector

This can be either coiled ‘Slinky’ or straight pipes that are buried up to 2m deep in open ground (your garden). The pipe is usually plastic and contains a Glycol antifreeze solution.

Slinky

The name sometimes used to describe the type of ground collector pipes which are coiled before burying in a trench.     

Borehole

This is simply a vertical hole drilled in the ground. A ground source collector pipe can be installed into this.

Open Loop

This is the type of source where river or ground water is pumped through a heat pump then expelled to the environment a few degrees colder.

Closed loop

This is where a sealed plastic ground pipes are used which usually contains a glycol antifreeze. This is the most common trench or borehole ground source heat pump system.

DX system

Abbreviation for ‘direct expansion’. This is where the refrigerant flows directly within the ground pipes. This system is less common, and may have some disadvantages.

Antifreeze

An additive that lowers the freezing point of water. Ethylene or Propylene Glycol are most commonly used in heat pump systems.

Brine

Brine is normally defined as ‘salt water’. However, this term seems to be have adopted to describe any antifreeze mixture. A brine-water heat pump usually means one having glycol antifreeze on the ‘cold’ side and water on the ‘hot’ side.

Emitters or ‘heat emitters’

Another term used to describe radiators or underfloor heating. This is the component that emits the heat into the building.

Sink

Abbreviation of ‘heat sink’. This is the name sometimes given to the part where the heat is usefully dissipated, such as radiators in the room, underfloor heating etc. ‘Heat load’ or ‘heat emitter’ are other terms

DHW    Domestic Hot Water

This the stuff that comes out of your taps. With heat pumps it is always stored in a DHW cylinder. Combi-boilers are direct gas water heaters with no storage cylinder.

Buffer tank

This is simply a large water cylinder that may be used to improve the efficiency by reduces the number of stop/starts that the compressor makes, and ensures a high water flow-rate through the heat pump. However, buffer tanks can introduce inefficiencies too. Modern variable-speed heat pumps tend not to need a buffer cylinder. A small buffer tank may also be needed to help with the defrost cycle of an air source heat pump.

Refrigerant

This is the working fluid within the heat pump. It evaporates in the ‘cold’ part and condenses in the ‘hot’ part. By doing so, heat is transferred from cold to hot. This fluid is sealed in, and should not leak or degrade within the life of the heat pump.

Heat Exchanger

This is a simple component that transfers heat from one fluid to another. It could be liquid to liquid, liquid to air, air to air. Two heat exchangers are housed within the heat pump, one for the ‘hot’ side (the condenser), and the other for the ‘cold’ side (the evaporator).

De-superheater

This is an extra small heat exchanger fitted to the compressor discharge pipe that can produce a small amount of heat at a higher temperature. If fitted, it can heat domestic hot water to a high temperature whilst also room heating or cooling

Passive Cooling

Passive cooling is where the ground water is simply pumped around underfloor heating. This gives limited amount of ‘free cooling’. It will only be effective with boreholes or large trenches in wet ground. Whilst it may have a limited effect, it can be almost free!

Passive heat recovery ventilation

This is where the out-going exhaust air passes its heat to the incoming fresh air with only the use of a simple heat-exchanger. It uses no heat pump.

Buffer tank

This is simply a large water cylinder that may be used to improve the efficiency by reduces the number of stop/starts that the compressor makes, and ensures a high water flow-rate through the heat pump. However, buffer tanks can introduce inefficiencies too. Modern variable-speed heat pumps tend not to need a buffer cylinder. A small buffer tank may also be needed to help with the defrost cycle of an air source heat pump.

Heat Pump Capacity Rating

A heat pump is given a kW heat output rating. This value will vary depending on the working temperatures. The electrical power input will very roughly be between a 1/2 and a 1/5 of the heat output . E.g. a 5kW heat pump will produce nominally 5kW of heat, and require typically between 1 and 2.5kW electrical input, depending on operating temperatures.

Inverter

This is a sophisticated electrical device that can vary the output capacity of a heat pump. It therefore can vary the heat output to match the heat demand. (An inverter also acts as a soft-start)

Set-back

Night set-back is the amount you reduce the heating at night (or in the daytime when you are out). We usually reduce the setting only a few degrees at night when a heat pump is used.

Heating Curve

Almost all heat pumps, and many condensing boilers control the heated water temperature (to the radiators etc) using a Heating Curve.  To explain –  It makes sense to have the radiators warmer when its colder outside.  Each manufacturer has a different number setting.  Read your user manual for a description relating to your product

Soft Start

This is an electrical device that reduces the start surge that is taken by a conventional compressor. It does not save energy, but stops lights flickering, and may reduce wear & tear.

Deemed

This term is used in RHI payment calculations. It is the amount of energy a building is estimated to use over a year. It is calculated by an Energy Assessor for use in and EPC (Energy Performance Certificate)


Some useful figures and conversions

1 kW (kilowatt) is a unit of Power or a rate of energy. (A 1 bar fire consumes 1 kW)

There are 3,411 Btu’s in 1 kWatt. i.e.10kWatts = 31,400 Btu/hr.

There are 860 kcal/hr in 1 kW

A normal immersion heater uses 3kW when heating


1 kWh. (kilowatt hour) is a quantity of energy

( A 1 kW heater would use 24kWhr per day )

I kWatt Hr. = 1 unit of electricity = 1 bar fire used for one hour.

1 kJoule x 3,600 = 1 kWhr.

Note heat pumps are rated by their heat output, not their electricity input.


If 10Kwatts were extracted from water having a flow rate of 0.8Lit/sec then the temperature would drop by 3°C (3K).

A heat pump with a heat output of 10kW and a COP of 4 can be represented by the following equations:-

COP = heat output / electricity consumption

10kW / 2.5kW = COP of 4

the heat extracted from the ground = heat delivered – electricity consumption = 10kW – 2.5kW = 7.5kW

0°C = 32°F (freezing point of water)

10°C = 50°F

20°C = 68°F (room temperature)

100°C = 212°F (boiling point of water)

or, if you have a calculator, °F-32,/9,x5=°C, °Cx9,/5,+32=°F

1 lit/sec = 3.6m³/Hr. = 13.19 Galls(UK)/min.

This chart gives an indication of flow rates for a 10kw (heat output) heat pump taking heat from a river or spring source.

(the extracted heat has been assumed to be 7.5kW)

In our example, for a river source system, the flow rate would need to be at least 0.6 litres/ second to minimise the risk freezing in the evaporator.   For a spring source, the flow rate would ideally be the same, but if the supply was limited, or pumping used a lot of energy, then half that rate may suffice.

Note, these are example values. Manufacturer’s data should be available for specific equipment.

Water purity for normal copper-brazed stainless heat-exchangers as used in almost all heat pumps.

The following list will give some idea of the requirements. Check with the heat pump manufacturer to get specific data relating individual heat pumps.

Sulphate < 100 mg/l  Free chlorine < 0.5 mg/l   Chloride < 300 mg/l   Nitrate < 100 mg/l   pH value 6.5 – 9   Electr. conductivity 50 – 1000 µS/cm    Oxygen < 2 mg/l